Specifications
Humidity Transducer
- Accuracy*: ± 3% RH (30% to 70% RH)
- Range: 0-100% RH
- Hysteresis: ± 1%
- Supply Voltage: 12-40 VDC / 12-35 VAC (VDC output units only)
- Compensated Temperature Range: -30°F to 130°F (-35°C to 55°C)
- Load Impedance: 1.5K ohms max. at 40 VDC (mA output units)
1K ohms min. (VDC output units)
* Includes non-linearity and non-repeatability
Platinum RTD Sensor
- Accuracy: 0.12% at 0°C
- Resistance: 100 or 1,000 ohm at 0°C
- Standard: DIN 43760
- Heat Dissipation: 3.0 mW/°C
- R/T Characteristics: Refer to TI.700-11 (See Temperature Sensor section)
- Operating Temperature Range: -30°F to 130°F (-35°C to 55°C)
Thermistor Sensor
- Interchangeability: ± 0.2°C
- Heat Dissipation: 3.0 mW/°C
- R/T Characteristics: Refer to TI.700-11 (See Temperature Sensor section)
- Operating Temperature Range: -30°F to 130°F (-35°C to 55°C)
General
- Environmental: 10 - 100%RH
- Enclosure: 20% glass filled polycarbonate
- Bracket: 18 Ga galvanized steel
- Termination: 1/4" quick disconnect terminals
- Wire Size: 12 Ga maximum
- Weight: 0.5 lbs. (.20 kg)
Conformance & Testing
RoHS Compliant
EMC Testing:
BS EN 55022:1998, BS EN 55024:1998,
EN 61000-3-3, EN 61000-4-2,
EN 61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN 61000-4-6,
EN 61000-4-11
|